Question

Hello, please tell me how the system should look like: us on a horizontal receiver 250l need to put two safety valves, respectively, need a switching valve. It is screwed directly to the receiver or adapter is needed? The valves are screwed directly into the valve or with an adapter?

It all depends on the switching valve that you are going to use. The parameters of the switching valve should be as follows Rotalock UNF 1 1/4 "(port of the safety valve on the container) NPT 3/8" (connection safety valve) NPT 3/8 "(connection safety valve). In this case, the adapters is not required.
P.S .: diverter valve FP-TV-114-038 with these parameters is currently being tested, is expected to release 06/2016, which will be announced in the news.

Answer
Hello, please tell me how the system should look like: us on a horizontal receiver 250l need to put two safety valves, respectively, need a switching valve. It is screwed directly to the receiver or adapter is needed? The valves are screwed directly into the valve or with an adapter?

It all depends on the switching valve that you are going to use. The parameters of the switching valve should be as follows Rotalock UNF 1 1/4 "(port of the safety valve on the container) NPT 3/8" (connection safety valve) NPT 3/8 "(connection safety valve). In this case, the adapters is not required.
P.S .: diverter valve FP-TV-114-038 with these parameters is currently being tested, is expected to release 06/2016, which will be announced in the news.